202
mbusm exccond e
*This is command is used when CTM200 is being used as a MODBUS Master*
Set the condition that will trigger MODBUS exception reports.
e = 0 Disable the MODBUS exception reports (default)
e = 1 to 7FFF in hex MODBUS events and exceptions to be used
MODBUS Event and Exception Bitmap:
bit0
Illegal Function Exception, Code 1 A master sends a Modbus function,
which is not supported by the slave device.
bit1
Illegal Address Exception, Code 2 A master queries an invalid or
non-existing data address.
bit2
Illegal Value Exception, Code 3 A master sends a data value, which is
not an allowable value for the slave device.
bit3
Slave Failure Exception, Code 4 An unrecoverable error occurs in the
slave device. The length might exceed the allowable data size.
bit4
Acknowledge Exception, Code 5 A long duration of time will be required
to process the request. This is to prevent a timeout error.
bit5
Slave Device Busy Exception, Code 6 A long?duration program
command is running. The command should be retransmitted later.
bit6
NAK Exception, Code 7 The slave cannot perform the program function
received in the query.
bit7
Memory Parity Error Exception, Code 8 A master attempted to read
record file, but detected a parity error in the memory.
bit8
Gateway Path Unavailable Exception, Code 10/0x0A The gateway is
unable to establish a connection with the target device.
bit9
Gateway Target Fail Exception, Code 11/0x0B The gateway is unable to
receive a response from the target device. Usually means that the device
is not present on the network.
bit10
Reply Timeout Event, Code 12/0x0C The slave device does not reply in
time or does not reply at all. The device ID might be wrong.
bit11
Send Timeout Event, Code 13/0x0D The handshake lines are not
properly set.
bit12
Device Open Error Event, Code 14/0x0E The Modbus Master couldn't
open a serial or TCP slave device. The network is down, or the serial port
is already opened. The function code in $PMEX will be 0 for this event.
bit13
TCPIP Connection Closed Event, Code 15/0x0F TCP/IP connection was
closed by the remote slave device.
bit14
Unknown Poll Error Event, Code 16/0x10 This event is for all other
errors when polling slave devices.
At least one event or exception defined by e should be detected to trigger reports. The exception code 12 ~ 16 are defined by Cypress Solutions.
See also: [MODBUS]