3 3BMODBUS Configuration Commands
MODBUS messages can be configured to be sent as MODBUS RTU messages encapsulated in UDP
packets, or as MODBUS TCP messages. MODBUS RTU over UDP messages minimizes wireless data usage
at the cost of unreliable data delivery. MODBUS TCP messages provide reliable data delivery at the cost of
increased wireless data usage. The default configuration for the modem in MODBUS mode is to use
MODBUS TCP as the over-the-air protocol.
2 MODBUS Configuration Commands
The following section details the modem specific commands used to configure the modem as either a
MODBUS slave gateway or a MODBUS master gateway.
Note: For all commands to be saved to non-volatile memory, a “cmd save” must be entered before
turning off or restarting the modem.
2.1 MODBUS Serial Master Gateway Modem Configuration
The following set of modem commands will configure the modem to act as a MODBUS serial master
gateway using MODBUS RTU between the MODBUS master application and the modem, and using
MODBUS RTU over UDP over-the-air.
cmd factory Reset modem configuration to factory defaults
cmd modbusctm130 1 Set modem to use MODBUS RTU over UDP over-the-air
to maintain backward compatibility with CTM13x modems